Page 20 - 浙江中盛电力设备有限公司
P. 20
S13
系列油浸式变压器
Series of oil-immersed transformer
S13-M 系列 20kV 级三相双绕组无励磁调压配电变压器
S13-M series of 20 kv three-phase double winding non-field excitation changer distribution transformer
电压组合及分接范围
Voltage Combinationand Tap range 空载电流 短路阻抗
额定容量 联结组标号 空载损耗 负载损耗
Rated capacity Vector No-load Load loss No-load Short circuit
(kVA) 高压 高压分接范围 低压 Group Symbol loss(W) (W) current impedance
High pressure High pressure Low pressure (%) (%)
(kV) tap range (% ) (kV)
30 80 690/660 2.1
50 100 1010/960 2
63 110 1200/1150 1.9
80 130 1440/1370 1.8
100 150 1730/1650 1.6
125 170 2080/1980 1.5
5.5
160 200 2540/2420 1.4
200 240 3000/2860 1.3
250 20 Dyn11 290 3520/3350 1.20
315 22 ±2×2.5 0.4 Yzn11 340 4210/4010 1.10
±5
400 24 Yyno 410 4970/4730 1.00
500 480 5940/5660 1.00
630 570 6820 0.90
800 700 8250 0.80
1000 830 11330 0.70
1250 970 13200 0.70 6.0
1600 1170 15950 0.60
2000 1550 19140 0.60
2500 1830 22220 0.50
S13-M 系列 35kV 级三相双绕组无励磁调压配电变压器
S13-M series of 35 kv three-phase double winding non-field excitation changer distribution transformer
电压组合及分接范围
Voltage Combinationand Tap range 空载电流 短路阻抗
额定容量 联结组标号 空载损耗 负载损耗
Rated capacity Vector No-load Load loss No-load Short circuit
(kVA) 高压 高压分接范围 低压 Group Symbol loss(W) (W) current impedance
High pressure High pressure Low pressure (%) (%)
(kV) tap range (% ) (kV)
50 130 1200/1140 1.05
100 185 2010/1910 0.90
125 215 2370/2260 0.90
160 225 2820/2680 0.80
200 270 3320/3160 0.80
250 320 3950/3760 0.75
315 380 4750/4530 0.75
400 35 ±2×2.5 Dyn11 460 5740/5470 0.65
500 38.5 ±5 0.4 Yyn0 540 6910/6580 0.65 6.5
630 660 7860 0.50
800 780 9400 0.50
1000 920 11500 0.50
1250 1120 13900 0.45
1600 1350 16600 0.45
2000 1590 19700 0.40
2500 1890 23200 0.40
注 : 对于额定容量为 500kVA 及以下的变压器 , 表中斜线上方的负载损耗值适用于 Dyn11 或 Yzn11 联结组 , 斜线下方的负载损耗值适用于 Yyno 联结组 .
Note: for the rated capacity of 500 kva and below transformer, load loss value of the diagonal lines in the table above apply to Dyn11 or Yzn11 link group, slash at the bottom of
the load loss value applies to Yyno link group.