Page 20 - 浙江中盛电力设备有限公司
P. 20

S13


                                                                                              系列油浸式变压器
                                                                                 Series of oil-immersed transformer


           S13-M 系列 20kV 级三相双绕组无励磁调压配电变压器
           S13-M series of 20 kv three-phase double winding non-field excitation changer distribution transformer


                                    电压组合及分接范围
                              Voltage Combinationand Tap range                                 空载电流      短路阻抗
            额定容量                                               联结组标号       空载损耗      负载损耗
            Rated capacity                                       Vector    No-load  Load loss  No-load  Short circuit
            (kVA)           高压        高压分接范围          低压      Group Symbol  loss(W)   (W)       current  impedance
                        High pressure  High pressure  Low pressure                               (%)       (%)
                            (kV)      tap range (% )  (kV)
            30                                                               80      690/660     2.1
            50                                                               100    1010/960      2
            63                                                               110    1200/1150    1.9
            80                                                               130    1440/1370    1.8
            100                                                              150    1730/1650    1.6
            125                                                              170    2080/1980    1.5
                                                                                                           5.5
            160                                                              200    2540/2420    1.4
            200                                                              240    3000/2860    1.3
            250              20                                  Dyn11       290    3520/3350    1.20
            315              22         ±2×2.5         0.4       Yzn11       340    4210/4010    1.10
                                          ±5
            400              24                                  Yyno        410    4970/4730    1.00
            500                                                              480    5940/5660    1.00
            630                                                              570      6820       0.90
            800                                                              700      8250       0.80
            1000                                                             830     11330       0.70
            1250                                                             970     13200       0.70      6.0
            1600                                                            1170     15950       0.60
            2000                                                            1550     19140       0.60
            2500                                                            1830     22220       0.50
           S13-M 系列 35kV 级三相双绕组无励磁调压配电变压器
           S13-M series of 35 kv three-phase double winding non-field excitation changer distribution transformer


                                    电压组合及分接范围
                              Voltage Combinationand Tap range                                 空载电流      短路阻抗
            额定容量                                               联结组标号       空载损耗      负载损耗
            Rated capacity                                       Vector    No-load  Load loss  No-load  Short circuit
            (kVA)           高压        高压分接范围          低压      Group Symbol  loss(W)   (W)       current  impedance
                        High pressure  High pressure  Low pressure                               (%)       (%)
                            (kV)      tap range (% )  (kV)
            50                                                               130    1200/1140    1.05
            100                                                              185    2010/1910    0.90
            125                                                              215    2370/2260    0.90
            160                                                              225    2820/2680    0.80
            200                                                              270    3320/3160    0.80
            250                                                              320    3950/3760    0.75
            315                                                              380    4750/4530    0.75
            400              35         ±2×2.5                   Dyn11       460    5740/5470    0.65
            500             38.5          ±5           0.4       Yyn0        540    6910/6580    0.65      6.5
            630                                                              660      7860       0.50
            800                                                              780      9400       0.50
            1000                                                             920     11500       0.50
            1250                                                            1120     13900       0.45
            1600                                                            1350     16600       0.45
            2000                                                            1590     19700       0.40
            2500                                                            1890     23200       0.40
           注 : 对于额定容量为 500kVA 及以下的变压器 , 表中斜线上方的负载损耗值适用于 Dyn11 或 Yzn11 联结组 , 斜线下方的负载损耗值适用于 Yyno 联结组 .
           Note: for the rated capacity of 500 kva and below transformer, load loss value of the diagonal lines in the table above apply to Dyn11 or Yzn11 link group, slash at the bottom of
           the load loss value applies to Yyno link group.