Page 15 - 浙江中盛电力设备有限公司
P. 15
S11
系列油浸式变压器
Series of oil-immersed transformer
S11 系列 10kV 级三相双绕组无励磁调压电力变压器
S11 series 10kV three - phase dual - winding non - excitation voltage regulator power transformer
电压组合及分接范围
短路阻抗
额定容量 Voltage Combinationand Tap range 联结组标号 空载损耗 负载损耗 空载电流 Short circuit
No-load
Rated capacity 高压 高压分接范围 低压 Vector No-load Load loss current impedance
(kVA) High pressure High pressure tap Low pressure Group Symbol loss(W) (W) (%) (%)
(kV) range (% ) (kV)
630 820 6920 0.60
800 1000 8460 0.60
1000 1180 9910 0.60
6
3
1250 6.3 3.15 1400 11700 0.50
1600 10 6.3 1680 14100 0.40
10.5
2000 ±2×2.5 Yd11 2010 16900 0.40 5.5
±5 Dyn11
2500 2370 19600 0.40
3150 2800 23000 0.40
4000 3450 27300 0.40
10 3.15
5000 4100 31300 0.40
10.5 6.3
6300 4890 35000 0.40
SZ11-M 系列 10kV 级三相双绕组有载调压配电变压器
SZ11-M series 10kV three-phase double-winding on-load tap-changer distribution transformer
电压组合及分接范围
短路阻抗
额定容量 Voltage Combinationand Tap range 联结组标号 空载损耗 负载损耗 空载电流 Short circuit
No-load
Rated capacity 高压 高压分接范围 低压 Vector No-load Load loss current impedance
(kVA) High pressure High pressure tap Low pressure Group Symbol loss(W) (W) (%) (%)
(kV) range (% ) (kV)
200 380 2900 1.00
250 440 3420 0.90
315 530 4100 0.90 4.0
400 640 4950 0.80
500 760 5890 0.80
6
630 6.3 ±4×2.5 0.4 Dyn11 960 7260 0.60
800 10 Yyn0 1120 8890 0.60
10.5
1000 1360 10400 0.60 4.5
1250 1560 12300 0.50
1600 1920 14700 0.50
2000 2270 18600 0.40
5.0
2500 2680 21600 0.4
注 1: 对于额定容量为 500kVA 及以下的变压器,表中斜线上方的负载损耗值适用于 Dyn11 联结组,斜线下方的负载损耗值适用于 Yyn0 连接组。
Note 1: Rated capacity 500KVA and below transformer, the load loss above the oblique line in the table applies to Dyn11 or Yzn11; the load loss below the oblique line applies to Yyn0.
06 Page