P. 15

MVG2-12                  型高压真空断路器

                                   Type High Voltage Vacuum Circuit Breaker


            MVG2

            固封式高压真空断路器 主要技术参数

            Enclosed Type HV Vacuum Circuit Breaker Main Technical Parameters
                                                                                                                                  储能电机技术参数
                                项   目 Item                     单位 Unit             技术数据 Technical data
           额定电压 Rated voltage                                     kV     12                                                       Energy Storing Motor
                          额定短时工频耐受电压(1min)                        kV     42
           额定绝缘水平         Rated power-frequency short-duration withstand voltage(1min)                                                                                                      正常工作电压范围          额定电压下的储能时间(S)
           Rated insulation level  额定雷电冲击耐受电压(峰值)                 kV     75                                                              型号           额定电压(V)         额定输入功率(W)
                          Rated lightning impulse withstand voltage (peak value)                                                        Model         Rated voltage    Rated power input    The range of normal    Energy storage time
           额定频率 Rated frequency                                   Hz     50                                                                                                                  working voltage       under rated voltage
                                                                         630     630     1250    1250                                                    DC110V                            85%~110% 额定电压
                                                                         1250    1250    1600    1600                                   ZYJ55-1          DC220V             70 , 100       85%~110%Rated voltage        ≤ 15
                                                                                         2000    2000
           额定电流 Rated current                                     A
                                                                                         2500    2500
                                                                                         3150    3150     3150
                                                                                         4000    4000     4000
           额定短路开断电流 Rated short-circuit breaking current          kA     20      25      31.5    40       50                      合、分闸电磁铁及相关电气元件技术参数
           额定短时耐受电流  Rated short-time withstand current           kA     20      25      31.5    40       50                      Technical Parameters of the Closing and Opening Elecromagnet and Related Components

           额定峰值耐受电流  Rated peak withstand current                 kA     50      63      80      100      125
           额定短路关合电流(峰值)Rated short-circuit making current (peak value)  kA  50   63      80      100      125                               类别 Category     合闸电磁铁                分闸电磁铁                 闭锁电磁铁             防跳继电器

           4s热稳定电流   4s thermal stability current                 kA     20      25      31.5    40       50
                                                                                                                                   项目 Item              Closing electromagnet  Opening electromagnet  Latching electromagnet  Anti-trip relay
           额定动稳定电流 Rated dynamic current                          kA     50      63      80      100      125
                                                                                                                                    额定工作电压 (V)
           额定电容器组关合涌流  Rated capacitor bank inrush making current  kA    12.5 ( 频率不大于1000Hz/frequency not more than 1000Hz)         Rated operational voltage  DC220  DC110   DC220       DC110     DC220     DC110    DC220    DC110
           额定单个/背对背电容器组开断电流                                       A      630 / 400                                                  额定工作电流 (A)
           Rated single/back-to-back capacitor bank breaking current                                                                Rated operational current  1.1  2.2        1.1         2.2           25 mA             9.1 mA
           额定短路持续时间 Rated duration of short-circuit               S      4                                                          额定电功率 (W)
           二次回路工频耐受电压  Power-frequency withstand voltage of secondary circuit  V  2000                                              Electrical rating     242       242        242        242             2.7                1.0

           额定操作电压         合闸线圈 Closing coil                       V      AC 110 / 220  DC 110 / 220                                 正常工作电压范围            85%~110%额定电压       65%~120%额定电压低于30%
           Rated operational   分闸线圈 Opening coil                  V      AC 110 / 220  DC 110 / 220                                 The range of normal  85%~110% rated voltage  额定电压时,开关不能分闸
           voltage        储能电机 Energy-storage motor               V      AC 110 / 220  DC 110 / 220                                 working voltage                        When the 65%~120% rated voltage   -               -
                                                                                                                                                                           is less than 30% rated voltage,
           分闸时间(额定电压)  Opening time (rated voltage)               ms     20~50                                                                                             the switch cannot be opened.
           合闸时间(额定电压)   Closing time (rated voltage)              ms     30~70
           动、静触头允许磨损累计厚度                                         mm      3
           Permit abrasion total thickness of dynamic and static contacts
           储能时间 Energy storage time                               s      ≤ 15                                                     二次控制回路方案组合
           触头开距 Clearance between open contacts                  mm      9± 1
                                                                                                                                  Scheme of the Double-control Circuit
           接触行程 Contacting travel                                mm      3 ~4
           触头合闸弹跳时间  Jump time of contact close brake             ms     ≤ 2
           三相分、合闸不同期性  Three-phase opening, closing non-synchronism  ms  ≤ 2                                                          控制电压          闭锁方案           防跳方案         欠压脱扣方案                       过流脱扣方案
                     1                                                                                                                                                           Undervoltage
           平均分闸速度   Average opening speed  1                     m/s     0.9 ~1.3                                                   Control voltage  Blocking scheme  Anti-trip scheme  tripping scheme  Overcurrent tripping scheme
                     2
           平均合闸速度 Average closing speed  2                       m/s     0.4~1.0
           触头分闸反弹幅值 Contact opening rebound amplitude            mm      ≤ 2                                                                                                                               过流脱扣器数量        动作电流值

                                                                                                                                       AC 220V                                                             Quantity of    Action current value
                                                                         ≤ 55 (630A)                                                              带电气闭锁         带防跳继电器         带欠压脱扣          带过流脱扣器       overcurrent trippers
                                                                                                                                                  With electric   With anti-trip relay  With undervoltage   With overcurrent
           主导电回路电阻                                               μΩ      ≤ 45 (1250A)                                                             blocking                     tripper        tripper      2过流 / 3过流
           Main galvanic circle resistance                               ≤ 35 (1600A~2000A)                                            DC 220V                                                             2 overcurrent /  3.5 / 5 / 7.5 / 10
                                                                                                                                                                                                           3 overcurrent
                                                                         ≤ 25 (2500A以上 / above 2500A)
                                                                                                                                       AC 110V    不带电气闭锁       不带防跳继电器         不带欠压脱扣
                                                                                                                                                                                                             不带过流脱扣器
                                                                         2000±200 (20kA)                                                          Without electric   Without anti-trip relay  Without undervoltage   Without overcurrent tripper
           触头合闸接触压力                                               N      2400±200 (25kA)                                               DC 110V    blocking                     tripper
           Contact closing rebound amplitude                             3100±200 (31.5kA)
                                                                         4750±200 (40kA)
                     3
           额定操作顺序 Rated operating sequence  3                            分 Opening -θ- 合分 Closing opening -180s -合分 Closing opening
                                                                         50000 (31.5kA及以下 / 31.5kA and below)
           机械寿命 Mechanical life                                   次      20000 (40kA及以上 / 40kA and above)
       MVG2-12  1. 平均分闸速度是指断路器触头刚分后6mm的平均速度;                                                                                                                                                                                              MVG2-12
             The average opening speed refers to the average speed of 6mm after the circuit breaker contact is just opened;
            2. 平均合闸速度是指断路器触头全开距平均速度;
      12     The average closing speed refers to full clearance average speed of the circuit breaker contact;                                                                                                                          13
            3. 当额定短路开断电流<40kA时,θ=0.3s;当额定短路开断电流≥40kA时,θ=180s。
             When the rated short-circuit breaking current is <40kA, θ  =0.3s, when the rated short-circuit breaking current is ≥40kA,θ  =180s.