Page 152 - 温州西卡电器有限公司(WENZHOU XIKA ELECTRICAL CO.,LTD.)
P. 152

> SCM Series moulded case circuit breaker



                                          > Specification
                                             Type   Thermal magnetic release             Electronic release
                                                     Rated current    Note     Rated              Note
                                                        In(A)                current In(A)
                                                  12.5,16,20,25,32,40,  T fixed
                                          SCM-125                                -
                                                   50,63,80,100,125  M fixed
                                                   16,20,25,32,40,50,  T fixed or
                  SCM-125L/3P             SCM-160                adjustable (0.7~1In)  -
                                                   63,80,100,125,160  M fixed
                                                   100,125,160,180,  T fixed or
                                          SCM-250                 adjustable (0.7~1In)  -
                                                       225,250       M fixed
                                                     225,250,315,   T fixed or        I1=0.4 1   In AM3 PR211(L-LI)
                                          SCM-400                 adjustable (0.7~1In)  320,400
                                                       350,400       M fixed          I1=0.4 1   In AM3 PR212(LSI-LSIG)
                                                                    T fixed           Tripping between 1.05 1.3   I1
                                                                                                2
                                          SCM-630    400,500,630                630   (IEC60947-2) I t=constant
                                                                    M fixed           (Long-time overload protection)
                                                                    T fixed           I2=1-2-3-4-6-8-10   In
                                          SCM-800    630,700,800                800   t2=0.05s, 0.1s, 0.25s, 0.5s adjustable
                                                                    M fixed
                                                                                      (Short-circuit short time delay
                                                                             800,1000,  protection)
                                          SCM-1250       -             -
                                                                               1250   I3=1.5-2-4-6-8-10-12   In
                  SCM-250L/3P                                                         (Instantaneous short-circuit
                                                                             1000,1250,
                                          SCM-1600       -             -              protection)
                                                                               1600
                                                                                      I4=0.2-0.3-0.4-0.6-0.8-0.9-1   In
                                                                                      t4= 0.1s, 0.2s, 0.4s, 0.8s  adjustable
                                                                                      (Earth fault protection)
                                          Note: T-thermal  M-magnetic  L-long time  S-short time relay  I-instantaneous  G-earth fault SCM-125/
                                          160 In=12.5,16,20,32,40 magnetic protection that is fixed at 500A.

                                          > Accessories
                                          The external  accessories of the breaker
                                            Motor-driven operation device
                                          1) Wiring diagram of type CDM electromagnetic operation device(fitting AM3-125,160,250) see the
                                          following drawing (wiring diagram of the external accessories of the breaker in the dotted frame)
                   SCM-400L               Code description: SB  SB  stand for push button.(provided by users themselves) Number “1” “2”
                                                         1
                                                             2
                                          “3” stand for number of wiring terminals.
                                          Voltage rating: AC50Hz 230V 400V, DC 220V
















                  SCM-400L/3P                 SCM-1600L
           >E 141